Carbon monoxide (CO) is a colorless, odorless gas produced whenever fuel burns incompletely: wood, gas, oil, propane, pellets, charcoal, gasoline. Every chimney and vent in a house exists for one job, to carry combustion gases, including CO, outside. When that job fails because the flue is blocked, the liner is cracked, the chimney is the wrong size, or the house pulls air down the chimney instead of letting it rise, CO ends up in living space.
This guide explains exactly how chimney and venting failures cause CO exposure, which appliances and conditions are most risky, how to recognize symptoms, where to put alarms and which ones to buy, what to do when an alarm sounds, and how sweeps and heating contractors find and fix the underlying problem. Nine illustrative scenarios show the most common real-world patterns.
Key facts at a glance
- The CDC reports that more than 400 Americans die each year from unintentional, non-fire CO poisoning, more than 100,000 visit emergency departments, and more than 14,000 are hospitalized.
- A CDC analysis of 1999–2004 death certificates found deaths peak in December and January, with the average daily number of CO deaths about three times higher in January than in July or August.
- The EPA lists "leaking chimneys and furnaces" and "back-drafting from furnaces, gas water heaters, wood stoves, and fireplaces" among the main indoor CO sources.
- The CDC and CPSC recommend CO alarms on every level of the home and outside sleeping areas, battery-operated or with battery backup. The CDC says to replace them every 5 years or as the manufacturer directs.
- UL 2034 is the US safety standard for residential CO alarms.
- The CDC recommends having chimneys inspected or cleaned every year, because blockages can trap CO indoors.
How a chimney keeps CO out, and how it fails
A working chimney relies on draft: hot flue gases are lighter than the cooler air around them, so they rise and pull fresh combustion air into the appliance behind them. The U.S. Department of Energy calls this the "stack effect." Draft depends on four things:
- Heat in the flue. A cold flue drafts weakly. The DOE notes that when the chimney air is colder than the house air, the house can become "a better chimney than the chimney," pulling cold, smelly chimney air into the room.
- An open, correctly sized path. Blockages, collapsed tiles, nests and clogged caps reduce or stop flow. A flue much larger than the appliance needs cools gases too quickly.
- A sealed path. Cracks and gaps in liners let gases leak into walls, attics, adjacent flues and rooms.
- Pressure balance in the house. Exhaust fans, dryers, range hoods and tight construction can pull the house into negative pressure, strong enough to reverse the flow in a chimney.
Break any of these and CO can enter the house. With wood appliances, you usually also see and smell smoke, which acts as a warning. With gas appliances, combustion products are often invisible and have little odor, which makes gas furnaces, boilers and water heaters on failed chimneys the most dangerous combination.
Classification: the ten chimney and venting failures that cause CO
Each type below includes a definition, how to identify it, the typical 2026 cost of the fix (estimated from national price surveys, HomeGuide and Angi, unless noted) and when it applies.
1. Blocked flue
Definition. Something inside the flue restricts or stops flow: bird or squirrel nests, leaves, fallen tile pieces, a collapsed liner, heavy creosote, or debris from a deteriorating crown.
How to identify it. Smoke rolling into the room when a fire is lit; a gas appliance's draft hood spilling (a hand near it feels warm, moist air); a CO alarm; bird or animal sounds in spring and summer; pieces of tile in the firebox or at the cleanout.
Typical cost. Sweep and debris removal $130–$380; animal removal $200–$1,500; if tiles have collapsed, relining with a stainless liner $1,500–$5,000.
When it applies. Any chimney, especially uncapped chimneys and older clay-tile flues. Chimney swift nests are federally protected; see chimney codes and regulations.
2. Cracked, gapped or deteriorated liner
Definition. The flue liner (clay tile, metal or cast-in-place) has cracks, open joints or missing sections, so flue gases escape into the masonry and nearby spaces.
How to identify it. Only a camera (Level II inspection) confirms it. Clues include smoke smell in rooms away from the fireplace, staining on walls near the chimney, and CO alarms that sound when a furnace runs.
Typical cost. Level II inspection $250–$600; stainless liner $1,500–$5,000 (up to about $7,000 for large or complex jobs).
When it applies. Older clay-tile chimneys, chimneys that have had a chimney fire, chimneys exposed to acidic gas condensate, and chimneys that moved in earthquakes or settling.
3. Oversized or orphaned flue
Definition. A gas water heater or furnace connects to a flue that is too large for it, often because a second appliance was removed. Flue gases cool before reaching the top, draft weakly, and condense acidic moisture that eats mortar and tile.
How to identify it. A furnace was replaced with a high-efficiency model that vents through the wall, leaving the water heater alone in the chimney. White or rust staining at the base of the chimney, deteriorated mortar at the cleanout, water at the thimble, weak draft at the draft hood.
Typical cost. Aluminum or stainless liner sized for the water heater $1,500–$3,000 (estimate); some owners switch to a direct-vent or heat pump water heater instead.
When it applies. Any home where the number or type of appliances on a chimney changed. NFPA 211 requires a Level II inspection when appliances are added, removed, or replaced with one of different type, input or efficiency. See chimney inspection levels.
4. Backdrafting from negative house pressure
Definition. The house is at lower pressure than outdoors, so air flows down the chimney instead of up, carrying combustion gases into the house.
How to identify it. Smoke or odors come down the chimney when exhaust fans, a range hood, a clothes dryer or a central vacuum run; a gas appliance spills at the draft hood when the bathroom fans are on; the fireplace smokes when you light it but improves when you open a window.
Typical cost. Draft and pressure diagnosis $150–$400 (estimate); makeup air for large range hoods, outdoor combustion air, or switching to sealed-combustion appliances can range from a few hundred to several thousand dollars.
When it applies. Tight or newly weatherized houses, homes with powerful range hoods, basements with atmospherically vented appliances, fireplaces on exterior walls.
5. Cold-chimney startup spillage
Definition. When a fire is first lit or a gas appliance starts, the flue is cold and draft is weak, so gases spill until the flue warms.
How to identify it. Smoke puffs into the room during lighting; brief spillage at a gas draft hood for the first minute or two of a cycle.
Typical cost. Often behavioral (preheat the flue, crack a window). An insulated liner ($1,500–$5,000) or a taller chimney can help chronic cases.
When it applies. Exterior masonry chimneys, oversized flues, cold climates, short chimneys.
6. Damaged, disconnected or corroded connector
Definition. The pipe between the appliance and the chimney (connector or stovepipe) is loose, rusted through, sagging, sloped the wrong way, or pulled out of the thimble.
How to identify it. Visible gaps at joints, rust holes, soot around joints, missing screws. The IRC requires connectors to slope upward at least 1/4 inch per foot toward the chimney.
Typical cost. Connector replacement $100–$500 (estimate).
When it applies. Furnaces, boilers, water heaters and wood stoves, especially older installations and damp basements.
7. Gas logs and closed dampers
Definition. Vented gas logs installed in a wood fireplace require the damper to be open or permanently blocked open. A closed or partly closed damper sends combustion products into the room.
How to identify it. Gas log set installed but no damper clamp; soot on the fireplace face; headaches when the logs run.
Typical cost. Damper clamp or stop $50–$150 (estimate); damper repair $100–$250; replacement $160–$520.
When it applies. Fireplaces converted to gas logs. See gas fireplace service.
8. Clogged cap, spark arrestor or termination
Definition. The cap screen or vent termination is plugged with creosote, leaves, ice or snow, or a high-efficiency appliance's PVC vent outside the wall is buried by snow.
How to identify it. Visible buildup on the screen; draft problems that start in winter; a high-efficiency furnace that shuts down or short cycles after snowfall.
Typical cost. Cleaning included in a sweep; new cap $75–$850.
When it applies. Wood stoves burning wet wood (screens clog fast), snowy regions, homes with sidewall vents near grade.
9. Shared flue and cross-contamination
Definition. Two appliances share one flue, or two flues in the same chimney leak into each other through a missing divider (wythe), so exhaust from one appliance comes out of the other's opening.
How to identify it. Furnace odors from the fireplace; soot at a basement cleanout; smoke test shows smoke from one flue emerging in another.
Typical cost. Smoke test with Level II $250–$600; relining one or both flues $1,500–$5,000 each.
When it applies. Older multi-flue masonry chimneys. The IRC requires a masonry wythe at least 4 inches thick between adjacent flues in new work.
10. Wrong appliance for the chimney
Definition. An appliance vented into a chimney or vent not listed or sized for it: a wood stove connected to a gas vent, an insert pushed into a fireplace without a liner, an unvented gas log set installed in a factory-built fireplace not listed for it.
How to identify it. Data plates that do not match; missing permits; creosote in a pipe marked for gas.
Typical cost. Correct venting or appliance replacement, often $1,500–$6,000 (estimate).
When it applies. DIY installs, used appliances, flipped houses.
CO sources in the home, ranked by chimney connection
| Source | Vents through | Main chimney-related CO risk | Warning signs |
|---|---|---|---|
| Gas or oil furnace (80% efficiency, atmospheric) | Masonry chimney or metal B-vent | Blocked or deteriorated flue, backdrafting, cracked heat exchanger (appliance issue) | Spillage at draft hood, soot, CO alarm when heat runs |
| Gas water heater (atmospheric) | Chimney or B-vent, often shared with furnace | Orphaned in oversized flue; backdrafting from exhaust fans | Melted plastic near draft hood, rust at vent, spillage |
| Gas or oil boiler | Chimney | Oil soot clogging; flue deterioration from condensate | Soot at barometric damper, odors |
| Wood fireplace | Masonry or factory-built chimney | Smoldering fires with closed damper, blocked flue, negative pressure | Smoke in room, soot on mantel |
| Wood stove or insert | Liner or Class A chimney | Creosote blockage, clogged cap screen, leaky door gaskets | Smoke on reload, creosote flakes |
| Pellet stove | Pellet vent pipe | Unsealed vent joints, power outage stopping the combustion fan | Smoke smell, soot at pipe joints |
| Vented gas logs or gas fireplace | Chimney or direct vent | Damper closed, blocked vent, soot buildup from misaligned logs | Soot on glass or face, headaches |
| Gas range and oven | Not vented through chimney | Poor adjustment; the EPA reports levels near well-adjusted stoves of 5–15 ppm and 30 ppm or higher near poorly adjusted ones | Yellow flames, soot |
| Generators, vehicles, charcoal | None (outdoor use only) | Exhaust entering through openings, attached garages | CPSC documented at least 94 generator CO deaths in 2005, 47 of them during Hurricane Katrina outages |
Symptoms and exposure levels
Inhaled CO forms carboxyhemoglobin in the blood, which, as the EPA explains, inhibits the blood's ability to carry oxygen. Symptoms are easy to mistake for flu. The CDC lists headache, dizziness, weakness, upset stomach, vomiting, chest pain and confusion. The CDC warns that severe exposure can cause loss of consciousness and death, and that some people die before they ever notice symptoms, which is why a sleeping household depends on alarms.
| CO concentration (approx.) | Typical effect (CPSC guidance) |
|---|---|
| 0.5–5 ppm | Typical indoor level in homes without gas stoves (EPA) |
| 1–70 ppm | Most healthy people have no symptoms; people with heart disease may have chest pain |
| Above 70 ppm | Headache, fatigue and nausea become noticeable |
| 150–200 ppm and above | Disorientation, unconsciousness and death possible |
Clues that point to CO rather than flu:
- Symptoms improve when you leave the house and return when you come home.
- Several people (and pets) in the house feel sick at the same time.
- Symptoms start or worsen when the furnace, water heater, fireplace or stove is running.
- No fever.
Higher-risk groups. The CDC notes that infants, older adults, and people with chronic heart disease, anemia or breathing problems are more likely to get sick from CO. The CDC's 1999–2004 analysis found higher death rates among adults over 65 and men.
What the data shows
- Annual toll. More than 400 deaths, more than 100,000 emergency department visits and more than 14,000 hospitalizations per year from unintentional, non-fire CO poisoning (CDC).
- Seasonality. From 1999 to 2004, an average of 439 people died each year from unintentional non-fire CO poisoning. The average daily death count was 2.07 in January and 1.97 in December, versus 0.67 in July and August (CDC MMWR).
- Consumer products. CPSC estimates about 170 deaths each year from CO produced by consumer products, not counting vehicles.
- Heating season overlap. The months with the most CO deaths are the same months chimneys, furnaces and fireplaces run hardest.
Backdrafting and negative pressure in detail
Backdrafting is the most misunderstood CO pathway because the chimney itself can be in perfect condition. The problem is the house.
How it happens. Every cubic foot of air an exhaust device pushes out of the house must be replaced. If the house is tight and has no dedicated makeup air, the easiest replacement path can be down the chimney. The EPA names "back-drafting from furnaces, gas water heaters, wood stoves and fireplaces" as a leading indoor CO source. Common culprits:
| Exhaust device | Why it matters |
|---|---|
| Kitchen range hood, especially high-capacity models | Can remove large volumes of air quickly; the most common trigger in remodeled homes |
| Clothes dryer | Runs for long periods, often in the same basement as the water heater and furnace |
| Bathroom exhaust fans | Several running at once add up |
| Central vacuum systems vented outside | Short, strong bursts |
| Whole-house fans and attic fans | Can depressurize the living space if not enough windows are open |
| A second fireplace or wood stove | One chimney with a hot fire can pull air down a colder chimney |
| Stack effect in tall or multi-story homes | Warm air leaving upper floors pulls outdoor air in at the lowest level, including down a basement flue |
Why tight houses raise the risk. Air sealing and new windows save energy but reduce the leaks that used to supply combustion air. Atmospherically vented appliances (the kind with an open draft hood on top) were designed for leaky houses.
How professionals test for it. Energy auditors and heating contractors perform a worst-case depressurization test, often called a combustion appliance zone (CAZ) test: close exterior doors and windows, turn on every exhaust fan and the dryer, close or open interior doors to create the worst case, then fire each appliance and measure draft with a manometer and check for spillage and CO. A chimney sweep can do a simpler version during a Level II.
Simple homeowner check (not a substitute for testing). With the water heater running, hold a lit incense stick or smoke pencil near the draft hood's edge. The smoke should be pulled into the hood. Repeat with the range hood, dryer and bath fans on. If smoke is pushed away from the hood, stop using the exhaust devices together and call a heating contractor.
Fixes, from simplest to most thorough:
- Run large exhaust fans only with a window cracked open nearby.
- Add makeup air for large range hoods (many jurisdictions require it above a certain fan capacity; ask your building department).
- Supply outdoor combustion air to the appliance room.
- Reline an oversized flue so it drafts more strongly.
- Replace atmospheric appliances with sealed-combustion (direct-vent) or power-vented models, or electric heat pumps, which do not depend on chimney draft.
CO alarms: types, placement and maintenance
Types of CO alarms
| Type | How it works | Best use |
|---|---|---|
| Battery-only plug-free alarm | Runs on replaceable or sealed batteries | Bedrooms and hallways without outlets; easy retrofit |
| Plug-in with battery backup | Powered from an outlet; battery keeps it working in outages | Near sleeping areas where an outlet is available |
| Hardwired with battery backup | Wired into house power, often interconnected | New construction and renovations; some state laws require it (Minnesota's law requires hardwired with battery backup except in limited cases) |
| Combination smoke and CO | One device, two sensors | Reduces clutter; check that the unit carries both the smoke and CO listings |
| Interconnected (wired or wireless) | When one sounds, all sound | Large or multi-story homes; recommended by CPSC |
| Digital display or low-level monitor | Shows current or peak ppm reading | Useful for tracking intermittent spillage; peak memory helps diagnose |
Buy alarms listed to UL 2034, the US standard CPSC helped develop. Combination units should also be listed to the smoke alarm standard.
Where to put them
- Every level of the home and outside each sleeping area (CDC and CPSC).
- Inside bedrooms that contain a fuel-burning appliance, such as a gas fireplace, where state law or your code requires it. Minnesota, for example, requires alarms within 10 feet of each bedroom, or inside a bedroom with a fuel-burning appliance.
- In Illinois, state law requires alarms within 15 feet of every sleeping room.
- On the level with the furnace and water heater, but not right next to them.
- Avoid kitchens, and do not place alarms directly above fuel-burning appliances (CPSC); avoid bathrooms, dead-air corners and spots near open windows or fans.
- Follow the height recommendation in the alarm's instructions; manufacturers vary.
Maintenance
- Test monthly with the test button.
- Replace batteries at least twice a year if not sealed; the CDC suggests doing it when clocks change for daylight saving time.
- Replace the whole alarm at the end of its life. The CDC says every 5 years or per the manufacturer; many units chirp or display an end-of-life signal.
- Vacuum dust from vents.
- Keep the instruction sheet: it explains the difference between alarm, low-battery and end-of-life signals.
For state-by-state alarm laws, see the table in chimney codes and regulations.
What to do when a CO alarm sounds: step by step
- Do not ignore it and do not try to find the source. CPSC advises immediately moving to fresh air and calling 911.
- Get everyone out, including pets. If anyone is drowsy, confused or unconscious, call 911 immediately and tell the dispatcher you suspect CO poisoning.
- Call 911 or the fire department from outside. Fire departments respond to CO alarm calls and typically carry meters to check the house.
- Do not go back in until emergency responders say it is safe.
- Seek medical care for anyone with symptoms. Tell the doctor you suspect CO; a blood test can measure carboxyhemoglobin, and it drops once the person is in fresh air, so prompt testing matters.
- Have appliances shut off. Responders or the gas utility may shut off or tag appliances as unsafe. Do not restart them.
- Book the right professionals. A heating contractor for furnaces, boilers and water heaters (combustion analysis, heat exchanger check), and a certified chimney sweep for a Level II inspection of the flue, especially if the alarm sounded when an appliance was running.
- Fix the cause before resuming use. Get written findings: what was wrong, what was repaired, and a post-repair CO and draft test.
- Replace the alarm if it is near end of life, and add alarms where coverage was missing.
If the alarm chirps (not a full alarm): that is usually low battery or end of life. Read the unit's label to distinguish chirp patterns.
If you feel symptoms and there is no alarm: treat it the same way. Get out, call 911.
Prevention checklist
- UL 2034 CO alarms on every level and outside every sleeping area; interconnected if possible.
- Annual chimney inspection and sweeping as needed (CDC, NFPA 211, CSIA).
- Annual service for gas and oil furnaces, boilers and water heaters.
- Level II inspection after any appliance change on a chimney.
- Chimney cap with screen to keep animals out; check it is not clogged.
- Gas logs: damper clamped open or removed per the log set's instructions.
- Wood burned dry and hot; no smoldering overnight fires with the damper nearly closed.
- Exhaust fans tested for backdrafting against atmospheric appliances.
- Sidewall vents of high-efficiency appliances kept clear of snow, leaves and shrubs.
- No generators, grills or vehicles running in the garage or near windows and doors; the CDC advises keeping generators at least 20 feet from windows and doors.
- Never use a gas oven to heat the home.
Estimated costs of CO-related chimney and venting repairs
| Service | Estimated 2026 cost | Notes |
|---|---|---|
| CO alarm (UL 2034) | Tens of dollars per unit; more for hardwired or smart models | Buy several |
| Standard chimney sweep | $130–$380 | Includes Level I in most cases |
| Gas appliance flue sweep | $80–$150 | Often combined with appliance service |
| Level II inspection with camera | $250–$600 | Required after appliance changes |
| Heating system tune-up with combustion analysis | $100–$300 (estimate) | Heating contractor |
| Chimney cap | $75–$850 | Wide range by size and material |
| Damper repair or replacement | $100–$250 repair, $160–$520 replace | Fireplace flues |
| Stainless steel liner | $1,500–$5,000 (to about $7,000) | Fixes cracked or oversized flues |
| Animal or nest removal | $200–$1,500 | Not for protected chimney swifts during nesting |
| Makeup air system for range hood | Several hundred to several thousand dollars (estimate) | Varies by design and climate |
Ranges are estimates based on 2026 national surveys (HomeGuide, Angi) and vary by region.
Worked examples
The following are illustrative scenarios, not real customers. Costs are estimates based on 2026 national price ranges.
Frequently asked questions
21 answersChimneys and CO
Can a blocked chimney cause carbon monoxide poisoning?
Yes. A nest, fallen tiles, heavy creosote or a clogged cap slows or stops the flow of combustion gases, so they spill back into the house through the fireplace opening, stove or the draft hood of a gas furnace or water heater. The CDC recommends inspecting or cleaning chimneys every year for this reason. Blockages in flues serving gas appliances are especially dangerous because the exhaust is invisible and nearly odorless.
Can a wood-burning fireplace produce carbon monoxide?
Yes. Any incomplete combustion produces CO, and smoldering fires produce more of it. Risks rise when a fire burns down overnight with the damper partly closed, when the flue is blocked, or when the house is under negative pressure from exhaust fans. Smoke usually warns you with wood fires, but CO can still build to dangerous levels in a closed room. Keep a CO alarm outside bedrooms and never close the damper until the fire is completely out.
Can a chimney leak CO into the house even when the fireplace isn't used?
Yes, if the chimney has other flues. A furnace, boiler or water heater venting through a flue next to the fireplace flue can leak exhaust through cracked liners or missing dividers and out the fireplace opening, or through cracks into walls and attics. A smoke test during a Level II inspection ($250–$600) shows whether flues leak into each other. If the fireplace smells of exhaust when the furnace runs, stop using the furnace and call a heating contractor.
What does backdrafting mean?
Backdrafting is when air flows down a chimney or vent instead of up, carrying combustion gases into the house. It is usually caused by negative house pressure from range hoods, dryers and bath fans, a cold chimney, or a flue too large for its appliance. The EPA lists backdrafting from furnaces, water heaters, wood stoves and fireplaces as a major indoor CO source. A heating contractor can test for it with a manometer under worst-case conditions.
Why does my house smell like smoke when the kitchen fan is on?
Your range hood is likely pulling the house into negative pressure, and the easiest path for replacement air is down the chimney, bringing soot odors and, if an appliance is running, combustion gases. Crack a window when using the hood and test for spillage at gas appliances. Long-term fixes include makeup air for the hood, outdoor combustion air, or sealed-combustion appliances. See chimney smoke and draft problems.
Does a gas furnace need a chimney liner?
If it vents into a masonry chimney, the flue must be lined and sized for the appliance under the fuel gas codes; many old clay-lined flues are too large for modern furnaces or have deteriorated from acidic condensate. Before a gas appliance is connected or replaced, the IFGC requires the chimney to be examined and cleaned if it previously served solid or liquid fuel. A liner for gas usually costs $1,500–$3,000.
Symptoms and health
What are the first signs of carbon monoxide poisoning?
Headache, dizziness, weakness, nausea or upset stomach, vomiting, chest pain and confusion, according to the CDC. They are often mistaken for flu, but CO usually causes no fever, affects several people or pets at once, and improves when you leave the house. If an alarm sounds or several people feel sick at home, get everyone into fresh air and call 911.
How much carbon monoxide is dangerous?
CPSC guidance says most healthy people feel no symptoms at 1–70 ppm, though people with heart disease may develop chest pain. Above 70 ppm, headache, fatigue and nausea appear. At 150–200 ppm, disorientation, unconsciousness and death are possible. Exposure time matters as much as concentration. For comparison, the EPA reports typical indoor levels of 0.5–5 ppm in homes without gas stoves.
Who is most at risk from carbon monoxide?
Everyone is at risk, but the CDC identifies infants, older adults, and people with chronic heart disease, anemia or breathing problems as more likely to get sick. The CDC's 1999–2004 analysis of death certificates found higher CO death rates among adults over 65 and among men. Households with sleeping infants or older relatives should treat alarm placement outside every bedroom, and annual appliance and chimney service, as non-negotiable.
Can a gas fireplace give off carbon monoxide?
Yes. Direct-vent gas fireplaces are sealed from the room, but a damaged glass gasket, a blocked or disconnected vent, or misaligned logs that cause sooting can release CO. Vented gas logs in a masonry fireplace depend on an open damper and a clear flue. Unvented (vent-free) logs release combustion products into the room by design. Have gas fireplaces serviced annually and keep a CO alarm nearby. See gas fireplace service.
Alarms
Where should carbon monoxide detectors be placed?
The CDC and CPSC recommend alarms on every level of the home and outside each sleeping area. Some state laws are more specific, such as within 10 feet of bedrooms in Minnesota or within 15 feet of sleeping rooms in Illinois. Avoid kitchens and spots directly above fuel-burning appliances. Follow the manufacturer's height instructions. Add alarms inside any bedroom that has a fuel-burning appliance.
What is UL 2034?
UL 2034 is the US safety standard for single- and multiple-station carbon monoxide alarms, developed with involvement from the Consumer Product Safety Commission. Look for the UL 2034 listing on the package or the alarm itself. State laws that require CO alarms often specify this listing, as Minnesota does. Combination smoke and CO alarms should carry both the CO and smoke alarm listings.
How often should I replace a CO alarm?
The CDC says to replace CO alarms every 5 years or according to the manufacturer. Many alarms have a built-in end-of-life signal, a chirp or display message, and some sealed-battery models last longer; check the date on the back of the unit. Test monthly and replace batteries twice a year on models with replaceable batteries. Write the installation date on the alarm with a marker so everyone in the house knows when it is due.
Is a smoke detector enough to detect carbon monoxide?
No. A smoke-only alarm does not sense CO. You need a separate CO alarm or a combination smoke and CO unit listed for both. Many older homes have smoke alarms but no CO alarms, and many state CO laws apply only to new construction, rentals or sales, so existing owner-occupied homes may not be covered by law. Install them anyway.
Do I need a CO alarm if I only have electric heat?
If your home has any fuel-burning appliance (gas range, water heater, fireplace, wood stove, pellet stove) or an attached garage, yes. An all-electric home with no fireplace and no attached garage has lower risk, but CO can still enter from a generator running outside during outages or from a neighbor's exhaust in attached housing. Alarms are inexpensive insurance. Put at least one outside the sleeping area.
What to do
What should I do if my CO alarm goes off?
Get everyone, including pets, into fresh air right away. Call 911 from outside. Do not try to find the source and do not go back in until responders say it is safe. Seek medical care for anyone with symptoms. Before restarting any appliance, have a heating contractor check furnaces, boilers and water heaters, and have a certified sweep do a Level II inspection of the chimney if the alarm sounded while an appliance was running.
Will the fire department come for a CO alarm?
Yes. CO alarm calls are routine emergency calls. Responders typically ventilate the house, measure CO levels, and may shut off or tag appliances they suspect. They do not repair appliances or chimneys, so plan to call a heating contractor and a chimney sweep afterward. Ask responders what readings they found and where; that helps the repair professional. If responders tag an appliance as unsafe, leave it off until it is repaired.
My CO alarm went off and then stopped. Is it safe?
Not necessarily. CO levels can drop when an appliance cycles off or a door opens, then rise again. Treat any full alarm as real: leave, call 911, and have the source found. Some alarms store peak readings; share them with responders. If the unit is near the end of its life or chirping, replace it, but only after the house has been checked.
Prevention and costs
How can I prevent carbon monoxide from my chimney?
Have the chimney inspected every year and swept when needed; service gas and oil appliances annually; install a cap with a screen; get a Level II whenever appliances change; clamp the damper open for gas logs; test for backdrafting with exhaust fans on; keep sidewall vents clear of snow; and install UL 2034 alarms on every level and outside bedrooms. Most of these steps cost less than $400 per year combined.
How much does it cost to fix a chimney that is leaking CO?
It depends on the cause. A blockage or nest may cost $200–$600 to clear. A cracked or oversized flue usually needs a liner, $1,500–$5,000 (up to about $7,000 for complex jobs), based on 2026 national surveys. Backdrafting fixes range from free (opening a window) to several thousand dollars for makeup air or sealed-combustion appliances. Always get the cause diagnosed with a Level II inspection before paying for repairs.
Who do I call for a CO problem, a chimney sweep or an HVAC contractor?
Often both. A heating (HVAC) contractor checks the appliance itself: burners, heat exchanger, combustion analysis, draft hood spillage. A certified chimney sweep checks the flue: blockages, liner condition, sizing and cap. If the alarm sounded while the furnace or water heater was running, start with the heating contractor and gas utility; if a fireplace or stove was running, start with the sweep. See how to hire a chimney sweep.
Sources
Facts, figures and rules on this page were checked against these sources. Prices are estimates based on 2026 national surveys adjusted for local costs.
- 1.CDC, Carbon Monoxide Poisoning basics
- 2.CDC MMWR, Carbon Monoxide-Related Deaths, United States, 1999–2004
- 3.U.S. EPA, Carbon Monoxide's Impact on Indoor Air Quality
- 4.U.S. CPSC, Carbon Monoxide Questions and Answers
- 5.U.S. Department of Energy, Wood and Pellet Heating
- 6.NCSL, Carbon Monoxide Detector Requirements, Laws and Regulations
- 7.Minnesota Department of Public Safety, CO detection in residential occupancies
- 8.NFPA 211-2024 Chapter 15 committee input (Level II triggers)
- 9.NYC Fuel Gas Code §503.5.6, Inspection of chimneys
- 10.Seattle Residential Code 2021 (2021 IRC basis), Chapter 18 Chimneys and Vents
- 11.Seattle Residential Code 2021, Chapter 10
- 12.HomeGuide, Chimney Inspection Cost (2026)